Knowledge Centre / Standards

Recommended Lux Levels UK: The BS EN 12464-1:2021 Lux Level Chart

A single reference chart of maintained illuminance, glare limits and colour rendering for the spaces UK employers and landlords most often need to check, with notes on how to apply each value.

This chart brings together the recommended lux levels UK employers, landlords and designers work to, taken from BS EN 12464-1:2021 Lighting of work places – Indoor work places. Each figure is a maintained illuminance (Em): the average the lighting must still deliver on the task area just before cleaning or relamping is due, not what it delivers on day one. Alongside it are the glare limit (UGR, unified glare rating, where lower is stricter) and the minimum colour rendering index (Ra).

Use it as a quick reference, then check the exact task in the standard or use our required lux lookup tool. Where we are not confident of a value, we have left it out rather than guess.

How to read the chart

  • Em is the required maintained average over the task area. The 2021 edition also gives a higher "modified" value for cases where the task is harder, such as older workers, low-contrast detail or long durations. The chart shows the required (lower) value.
  • UGR is the maximum discomfort glare permitted. Offices and classrooms are typically 19; circulation areas allow 25 to 28.
  • Ra is the minimum colour rendering index of the light source. 80 is standard for occupied work spaces; 40 to 60 is acceptable for circulation and storage.
  • Uniformity (Uo), the minimum divided by the average, also applies. It is typically 0.40 for circulation and 0.60 for office tasks.

Offices and general building areas

Area or taskEm (lux)UGR limitRa minNotes
Writing, typing, reading, data processing5001980DSE work
Technical drawing7501680
Conference and meeting rooms5001980Lighting should be controllable
Reception desk3002280
Archives2002580
Corridors and circulation areas1002840Measured at floor level
Stairs, escalators, travelators1002540Good contrast on step edges
Toilets, washrooms, cloakrooms2002580Light each fully enclosed cubicle
Canteens and pantries2002280
Rest rooms1002280
Commercial kitchen5002280Food preparation areas

The 500 lux office figure applies to the task area, usually the desk at around 0.75 m. Surrounding areas can be lower but must step down gradually. CIBSE LG7 adds UK guidance on wall and ceiling brightness for comfortable offices.

Schools and education

Area or taskEm (lux)UGR limitRa minNotes
Classrooms, tutorial rooms5001980Raised from 300 lux in the 2021 edition
Classrooms for evening classes and adult education5001980
Lecture halls5001980Controllable lighting
Art rooms5001980
Art rooms in art schools7501990
School sports halls3002280

The 2021 increase for classrooms is the change we most often see catch schools out. Rooms designed to 300 lux under the older edition may pass a legacy check but fall short of the current standard. DfE BB90 sets the design expectations for school buildings. See our classroom lighting guide.

Warehouses, storage and logistics

Area or taskEm (lux)UGR limitRa minNotes
Store and stock rooms1002560200 lux if continuously occupied
Unmanned rack gangways20–40At floor level
Manned rack gangways1502260At floor level
Control stations1502280
Storage rack face200–60Vertical illuminance
Loading ramps and bays1502540
Dispatch and packing areas3002560

Rack face illuminance is measured on the vertical plane, so a warehouse can meet its floor-level figures and still fail at the upper beam labels. Our warehouse lighting standards page covers racking and high-bay layouts in detail.

Retail

Area or taskEm (lux)UGR limitRa minNotes
Sales area3002280Display accent lighting is extra
Till area5001980

Healthcare

Area or taskEm (lux)UGR limitRa minNotes
Wards: general lighting1001980At floor level
Wards: simple examinations3001980Switchable, at bed level
Examination and treatment1,0001990
Waiting rooms2002280

Healthcare lighting is also shaped by HTM and HBN guidance and SLL LG2. Night-time ward levels and observation lighting go beyond what a single table can capture. See healthcare lighting requirements.

Car parks (covered)

Area or taskEm (lux)UGR limitRa minNotes
In/out ramps (day)3002540Extends into the parking floor
In/out ramps (night)752540
Traffic lanes752540At floor level
Parking areas752540
Ticket office3001980Avoid reflections in glazing

Open-air car parks are covered by BS EN 12464-2:2024 (outdoor work places) and, for public lighting, BS 5489-1:2020, rather than the indoor tables above.

Recommended levels vs the legal minimum

BS EN 12464-1:2021 values are good-practice design standards, not legal limits in themselves. The legal duty is regulation 8 of the Workplace (Health, Safety and Welfare) Regulations 1992: "suitable and sufficient" lighting. HSE guidance HSG38 gives lower minimums, such as 200 lux average for work requiring perception of detail. In practice, HSE inspectors, insurers, landlords and fit-out specifications all treat BS EN 12464-1:2021 as the benchmark of what "suitable" looks like. Our guide to light levels in the workplace compares the two side by side.

Why measured values differ from the chart

  • Maintenance factor: a new installation should measure above Em, typically by 20 to 30%, to allow for depreciation.
  • Daylight: compliance is normally assessed on electric lighting alone, so surveys are often carried out after dark.
  • Layout changes: moved desks, new racking and partitions change what the task area receives.

Check your building against the chart

A chart tells you the target; only a measured survey tells you whether you hit it. Polarity Lux carries out calibrated lux surveys across London and the South East. Every room is reported against the BS EN 12464-1:2021 value for its task, with average, minimum and uniformity. Office and retail surveys start from £175 (single floor up to 250 m²), and warehouse and industrial surveys from £320. Book a lux survey.

Frequently asked questions

What is the recommended lux level for an office in the UK?

BS EN 12464-1:2021 recommends 500 lux maintained illuminance for writing, typing, reading and computer work, with a UGR limit of 19 and Ra 80. Corridors in the same building need 100 lux.

What lux level does a classroom need?

The 2021 edition of BS EN 12464-1:2021 recommends 500 lux for general classroom activities, up from 300 lux in earlier editions, with UGR 19 and Ra 80.

What lux level is recommended for a warehouse?

Store and stock rooms need 100 lux (200 lux if continuously occupied). Manned rack gangways need 150 lux at floor level, loading bays 150 lux and dispatch and packing areas 300 lux.

Are the lux levels in BS EN 12464-1:2021 a legal requirement?

Not directly. The law requires suitable and sufficient lighting under regulation 8 of the Workplace Regulations 1992. BS EN 12464-1:2021 is the recognised good-practice benchmark used to judge whether lighting is suitable.

What does maintained illuminance mean?

Maintained illuminance is the average lux level that must still be achieved on the task area at the end of the maintenance cycle, after lamp depreciation and dirt build-up. New installations should therefore measure higher than the chart value.